| MODEL |
SKADS-5512 |
SKADS-5524 |
| |
| OUTPUT |
DC VOLTAGE |
12V |
5V |
24V |
5V |
| RATED CURRENT |
3A |
3A |
2A |
2A |
| CURRENT RANGE |
0 ~ 4A |
0 ~ 4A |
0 ~ 2.5A |
0 ~ 4A |
| RATED POWER |
51W |
58W |
| RIPPLE & NOISE (max.) Note.2 |
100mVp-p |
100mVp-p |
100mVp-p |
100mVp-p |
| VOLTAGE ADJ. RANGE |
CH1:10.8 ~ 13.2V |
CH1:21.6 ~ 26.4V |
| VOLTAGE TOLERANCE Note.3 |
¡À1.0% |
¡À3.0% |
¡À1.0% |
¡À3.0% |
| LINE REGULATION |
¡À0.5% |
¡À0.5% |
¡À1.0% |
¡À0.5% |
| LOAD REGULATION |
¡À0.5% |
¡À0.5% |
¡À1.0% |
¡À0.5% |
| SETUP, RISE, HOLD TIME |
800ms, 50ms, 60ms/230VAC 1.6s, 50ms, 16ms/115VAC at full load |
|
|
| INPUT |
VOLTAGE RANGE |
88 ~ 264VAC 124 ~ 370VDC |
| FREQUENCY RANGE |
47 ~ 63Hz |
| EFFICIENCY (Typ.) |
74% |
74% |
| AC CURRENT |
1.6A/115VAC 1A/230VAC |
| INRUSH CURRENT (max.) |
COLD START 35A |
| LEAKAGE CURRENT |
<3.5mA / 240VAC |
| |
| PROTECTION |
OVERLOAD |
105 ~ 135% rated output power. |
| Protection type : Hiccup mode, recovers automatically after fault condition is removed. |
| OVER VOLTAGE |
CH1:5.75 ~ 6.75VDC |
| Protection type : Shut down o/p voltage, re-power on to recover. |
| |
| ENVIRONMENT |
WORKING TEMP. |
-10 ~ +60¡æ (Refer to output load derating curve) |
| WORKING HUMIDITY |
20 ~ 90% RH non-condensing |
| STORAGE TEMP., HUMIDITY |
-20 ~ +85¡æ , 10 ~ 95% RH |
| TEMP. COEFFICIENT |
¡À0.03%/ (0 ~ 50) on +5V output |
| VIBRATION |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
| |
| SAFETY & EMC
(Note 4) |
SAFETY STANDARDS |
UL1950, TUV EN60950 Approved |
| WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
| ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC |
| EMI CONDUCTION & RADIATION |
Compliance to EN55022 (CISPR22) Class B |
| HARMONIC CURRENT |
Compliance to EN61000-3-2,-3 |
| EMS IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, Light industry level, criteria A |
| |
| OTHERS |
MTBF |
276.3K hrs min. MIL-HDBK-217F (25¡æ) |
| DIMENSION |
159*97*38mm (L*W*H) |
| PACKING |
0.57Kgs/pcs, 24pcs/13.7Kgs/0.75CUFT |
| |
| NOTE |
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of
ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wireterminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation. |
| |